Megapress S
Range
General
Flow-optimised press connector system made of non-alloy steel 1.0308 with an externally galvanised zinc-nickel coating for black, galvanised, industrially painted and powder-coated steel pipes. Press connector with stainless steel compression ring to ensure the mechanical strength of the connection. Suitable for concealed and pre-wall installations of manifold and riser pipes.
Labeling
Manufacturer, Pipe dimension, Batch, White dot on press end, Black rectangle with symbol »Not for potable water installations«, Detachable white label as press indicator
-
Show more
Press connector with Smart Connect Feature
Inadvertently unpressed connections are noticed immediately during a leakage test.
Viega guarantees the detection of unpressed connections in the following pressure ranges with water, compressed air or inert gases:
min. water pressure: 0.1 MPa / 100 kPa / 1 bar / 14.5 PSI
max. water pressure: 0.65 MPa / 650 kPa / 6.5 bar / 94.3 PSI
min. air pressure: 22 hPa / 2.2 kPa / 22 mbar / 0.3 PSI
max. air pressure: 0.3 MPa / 300 kPa / 3 bar / 43.5 PSI
Sealing elements for press connection
FKM (fluorocarbon rubber), matt black, pre-assembled
Note
The sealing materials of the press connector system are subject to thermal ageing, which depends on the media temperature and the operating time.
The higher the media temperature, the faster the thermal ageing of the sealing material progresses.
In the case of special operating conditions, e.g. industrial heat recovery systems, it is necessary to compare the specifications of the appliance manufacturer with the specifications of the press connector system.
Before using the press connector system beyond the areas of application described or if in doubt about the correct selection of material, please contact Viega.
Dimensions
D½–4, Size availability in accordance with the national regulations
Tools
The functional safety of Viega press connector systems depends primarily on the faultless condition of the press tools used. The Pressgun-Press Booster is required for pressingMegapress S XL-press connectors. Viega press tools have to be regularly maintained by authorised service partners.
Areas of application
Industrial and plant engineering
Local and district heating systems as per AGFW FW 524 (after entry into the building, ≤ DN50)
Closed cooling and heating systems
Compressed air systems
Fire extinguishing and sprinkler systems (the required minimum and maximum wall thickness have to be observed)
Systems for technical gases (request required)
Note
Use of the system for areas of application and media other than those described must be agreed in consultation with Viega. Detailed information concerning applications, limitations and national codes and standards can be found in the product documentation, either printed or on the Viega website.
Note – Standards and approvals
Suitable for steel pipes in accordance with Australian Standards AS 1074 (Light, Medium & Heavy) and US Standard pipes ASTM, A53, ASTM A106B & ASME B36.10M Schedule 5 to Schedule 40. NB: There are two ranges of DN65 (D2½) fittings as Australian Standard pipe has an outside diameter of 76.1 mm and US Standard pipe has an outside diameter of 73.0 mm. DN65 fittings with a model prefix of 42 should only be used with Australian Standard pipe. DN65 fittings with a model prefix of 48 should only be used with US Standard pipe.
Operating conditions
operating temperature -5 °C to +140 °C(2 3 °F to 284 °F)
The press connector systemMegapress S is designed for nominal pressure PN 16.
Materials press connector
Steel 1.0308
Note – Protection against external corrosion
Thanks to a zinc-nickel coating the press connectors are optimally protected against corrosion – e.g. when condensation forms in cooling systems.
The pipe being used should be protected with suitable corrosion prevention – observe manufacturer's information.
Pipes and pipe connectors should be insulated in the same way in accordance with the general rules of engineering.
Changes and errors excepted.
Latest Z- and installation dimensions as well as further technical information can be found on the Viega website and have to be checked before purchase, planning, construction work and use. Our products are continuously optimized.
This product description contains important information on choice of product and system, mounting, commissioning as well as intended use and, if required, on maintenance measures. This information on products, their features and application techniques is based on currently valid standards in Europe (e.g. EN) and/or in Germany (e.g. DIN/DVGW). Some passages in the text may refer to technical regulations in Europe/Germany. These should be considered as recommendations for other countries where no corresponding national requirements exist. The relevant national laws, standards, regulations, directives and other technical provisions take priority over the German/European directives specified in this product description: The information herein is not binding for other countries and regions and should be understood as recommendation.

certification
Article Number | certificate | certificate number |
country language |
||
---|---|---|---|---|---|
Article Number | certificate | certificate number |
country language |
Downloads